AA800 EZE QUICK INSTALLATION GUIDE Step by Step Installation Always refer to the installer’s manual to consult the references mentioned in this document and for further infor­mation. Main Menu Step 1. Installation Program Zones Set # of Zones View / Modify Zone Settings Outdoor Probe Phone Numbers (sec. 4.4) Auto-Test Schedule (sec. 4.9) Outdoor Probe (sec. 5.3) Output Relays (sec. 3.8.4) Siren Settings (sec. 3.5) Select a Zone (1-8) (sec. 5.4.1) Type: Temp (sec. 4.7) Low T° Set On-Site Listening (sec. 4.6) Hi T° Set High Noise Alarm (sec. 3.8.3) Activate / Bypass (sec. 5.5) System Self Test (sec. 3.8.5) (ch.10) Password Manag. (sec. 3.2) Event Buffer (sec.6.3) (sec. 3.7.3) Normal State (NO / NC) EOL Resistor (Y / N) (sec. 3.8.6) Change User (sec. 3.2.2) Help Menus (sec. 2.2) Install Programming (Default Password = 0801) Type: Burglar (sec. 3.7.3) Normal State (NO / NC) EOL Resistor (Y / N) (sec. 3.7) Program Dialer (sec. 4.3) Program Auxiliaries Main Menu System Auxiliaries User Preferences Voice ID System Message Make proper ground connections. A faulty earth ground connection immediately voids the system warranty without further notice (sec. 1.4.9). Step 8. Phone Call-in If there is an answering machine, or fax machine on the same line as the alarm system, activate the “Share Phone Line” option. To call the alarm system from another phone, dial the site number and allow the site phone to ring only 1 time and then hang up. Wait 15 seconds and redial the site number. The Agri-Alert will pick up the call after the first ring (sec. 4.7). Install the battery and then power up the Agri-Alert with the 16VAC wall transformer (note that the system will not boot when connecting the battery). Time betwen calls Install Programming Start call delay Use Program Wizard Main Menu View / Modify Phone Call-in Step 9. System Test As a final step, always perform a system test. A successful test tells the Agri-Alert is ready to operate. It is recommanded to perform this test on a regular basis (sec. 3.8.5). Below is a list of all programming steps of the Installation Wizard. Alarm recall delay Call repetitions Busy tries Pause delay key Tone delay Detect key phone? Dialout priority? Program Auxiliaries (sec. 4.8) (sec. 3.7.6) Relay Assigned Zones (sec. 3.7.5) Monitoring Select the menu below to record the site’s identification message (sec. 3.8.2). Main Menu How many phone #? Siren Enabled Zones Step 7. Recording Site ID Launch the Installation Wizard (sec. 3.1). Use dialout? Phone Enabled Zones Activate Zones Install and connect all zone sensors and the siren. If the alarm system uses the phone, connect the phone line to the Phone Plugin Card and then insert the card in the PHONE CARD port of the Agri-Alert. Likewise, if the system uses an outside temperature sensor, connect the sensor to the Outdoor Plugin Card and then insert the card in the OUTDOOR port of the Agri-Alert (see wiring diagram). These two plugin cards are optional (sec. 1.4). Step 5. Installation Wizard Program Dialer Message repetitions Program Zones Activate / Bypass Step 4. Power Supply User Preferences Software Version Main Menu Step 3. Earth Ground Recognition Time Recognition Time System Auxiliaries Update / Backup (sec. 3.7.4) Critical T° Set Type: Dry Contact (sec. 3.7.8) Step 2. Wiring # Next Phone Call-in Burglar Zone Delays (sec. 3.7.2) (sec. 5.5.2) Step 6. Activating Zones Install the Agri-Alert in a location where a telephone jack, a 120 volt AC power outlet, and proper grounding connections are readily available. (sec. 3.8.6) - Time & Date (sec. 3.3) - Units of Measurement (sec. 3.4) - Speaker Volume (sec. 3.6) - Installer Password (sec. 3.2) - Setup Zones (sec. 3.7) - Phone Numbers (sec. 4.3 & 4.4) - Burglar Arming Options (sec. 5.4) - Siren Options (sec. 3.5) - Outdoor T° Compensation (sec. 5.3) Main Menu Auto-Test Please scan the QR Code to access the complete manual or visit the website. Cumberland: http://www.cumberlandpoultry.com AP: http://www.automatedproduction.com REV 01 QUICK INSTALLATION GUIDE EN AA800 EZE AP (sec. 6.2) Cumberland Current Conditions #892-00068 REV 01 GSI Electronics Inc. • 5200 Armand Frappier Saint-Hubert, Qc • Canada J3Z 1G5 • Phone: 1-877-926-2777 E-mail: mtl_techsupport@agcocorp.com Page 1 AA800 EZE GUIDE D’INSTALLATION RAPIDE Installation par étapes Référez-vous au manuel de l’installateur pour consulter les références fournies dans ce document. Menu Princ. Étape 1. Installation Prog. des Zones Combien de Zones? Voir / Modifier Réglages des Zones Utilise Sonde Ext. (sec. 5.5.2) Numéros Tél. (sec. 4.4) Horaire D'auto-test (sec. 4.9) Sonde Extérieure (sec. 5.3) Sorties Relais Réglages de la Sirène Délais Zone de Vol (sec. 3.8.4) Suivant Sélectionner une Zone (1-8) (sec. 3.5) (sec. 5.4.1) Type: Temp Réception d'un Appel (sec. 4.7) Écoute à Distance (sec. 4.6) T° Haute Activer / Supprimer (sec. 3.8.3) (sec. 5.5) T° Critique Dél. Valid. Type: Contact Sec Auto Test du Système (sec. 3.8.5) Mise à Jour / Sauver (ch.10) Mots de Passe (sec. 3.2) Registre Événements (sec.6.3) Préférences Version du Logiciel (sec. 3.8.6) Changer D'utilisateur (sec. 3.2.2) Menus D’aide (sec. 2.2) (h:m:s) (sec. 3.7.3) État Normal Ferm / Ouv Résistance de Term. (Oui / Non) Dél. Valid. Système Auxiliaire (sec. 3.7.4) (h:m:s) Type: Antivol (sec. 3.7.3) État Normal Ferm / Ouv Résistance de Term. (Oui / Non) (Mot de Passe par Défaut = 0801) Prog. des Zones (sec. 3.7) Prog. du Téléphone (sec. 4.3) Prog. Auxiliaires (sec. 3.7.8) Menu Principal Activer / Supprimer Installez et branchez les détecteurs des zones et la sirène. Si un téléphone est utilisé, branchez la ligne à la carte enfichable pour téléphone puis insérez cette carte dans le port “PHONE CARD” de l’Agri-Alerte. De la même façon, si une sonde de température extérieure est utilisée, branchez la sonde sur la carte enfichable pour la lecture de température extérieure puis insérez cette carte dans le port “OUTDOOR” de l’appareil (consulter le schéma de branchement). Ces deux cartes sont optionnelles (sec.1.4). Étape 3. Mise à la Terre Effectuez une mise à la terre conforme de l’appareil. Une mise à la terre insufisante annule immédiatement la garantie sans préavis (sec. 1.4.9). Étape 4. Alimentation Branchez d’abord la batterie puis alimentez l’appareil avec le transfor­mateur mural 16 VCA (notez que le système ne démarrera pas lors de la connexion de la batterie). Étape 7. Message D’identification Sélectionnez le menu suivant pour enregistrer le message d’iden­tification du site (sec. 3.8.2). Menu Principal Système Auxiliaire Préférences Message Vocal Message Système Étape 8. Réception D’appel Si un répondeur ou un télécopieur partage la ligne télé­phonique de l’Agri-Alerte, activez le paramètre “Partage de la ligne”. Pour appeler un module Agri-Alerte qui utilise une ligne partagée, vous devez composer le numéro de téléphone du site, laisser sonner une seule fois puis raccrocher. Recomposez le numéro du site après 15 secondes, l’Agri-Alerte répondra dès la première sonnerie (sec. 4.7). Menu Principal Prog. du Téléphone Étape 5. Programmation Utilise tél.? Voir / Modifier Réception D’appels Lancez l’assistant de programmation (sec. 3.1). Combien de # tél. Délai interappel Installation Étape 6. Activation des Zones Activer une Zone Étape 2. Branchements # T° Basse Haut Niveau de Bruit (sec. 3.7.2) Installez le système d’alarme là où une prise de téléphone, une prise 120 volt CA, et les installation pour la mise à la terre sont facilement accessibles. Étape 9. Essai du Système Menu Principal Délai d’appel Avant d’utiliser votre système Agri-Alerte, effectuez un test sur l’appareil pour vous assurer de son bon fonctionnement. Il est recom­mandé d’effectuer ce test régulière­ment (sec. 3.8.5). Installation Répétition de message Assistant Program. Rappel Nombre de séquences Voici la liste des étapes parcourues par l’assistant : Essais ligne occupée - Date & Heure (sec. 3.3) - Unités de Mesure (sec. 3.4) - Volume du Haut-Parleur (sec. 3.6) - Mot de Passe Installateur (sec. 3.2) - Configuration des Zones (sec. 3.7) - Numéros de Tél. (sec. 4.3 & 4.4) - Paramètres D’armement (sec. 5.4) - Paramètres de la Sirène (sec. 3.5) - Compensation T° Extérieure (sec. 5.3) Touche pause Délai de tonalité Détecter touche tél? Prioriser appels ext? Prog. Auxiliaires Tél. Activé Pour Zone (sec. 4.8) Sirène Act. Pour Zone (sec. 3.7.6) Assignation de Relais (sec. 3.7.5) Supervision (sec. 3.8.6) Menu Principal Auto-test Système Veuillez scanner le code QR pour accéder aux manuels complets ou visiter le site Web. Cumberland: http://www.cumberlandpoultry.com AP: http://www.automatedproduction.com REV 01 GUIDE D’INSTALLATION RAPIDE FR AA800 EZE AP (sec. 6.2) Cumberland Conditions Courantes #892-00068 REV 01 GSI Electronics Inc. • 5200 Armand Frappier Saint-Hubert, Qc • Canada J3Z 1G5 • Phone: 1-877-926-2777 E-mail: mtl_techsupport@agcocorp.com Page 1