ABB Pin and Sleeve Mechanical Interlock Receptacles NSF Mode d'emploi

Ajouter à Mes manuels
4 Des pages
ABB Pin and Sleeve Mechanical Interlock Receptacles NSF Mode d'emploi | Fixfr
Pin and Sleeve Mechanical Interlock Receptacles in Watertight Enclosures
20A, 30A, 60A & 100A (Non-Fused)
20A, 30A, & 60A (Fused)
100A (Breakered)
INSTALLATION INSTRUCTIONS
•
•
•
•
FEATURES
Provides ON-OFF switched control of a directly connected load.
Meets the requirements of Outdoor/Indoor (IP67, Type 3R, 4X, Watertight, Corrosion resistant) and Indoor (Type 12K Dust tight) installations.
This enclosure provides lockout capability in compliance with OSHA Lockout/Tagout Regulation 29 CFR Part 1910.147 (in the OFF position) with an acceptable padlock/shackle, thereby assuring the connected equipment cannot be energized.
Auxiliary contact open prior to the line contacts for pilot duty switching.
NOTE: This enclosure must not be used as a junction box for feed-through connections.
WARNING
RISK OF SHOCK, DISCONNECT
POWER BEFORE INSTALLATION.
INSTALLATION INSTRUCTIONS
WARNING: FOR INSTALLATION ONLY BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) OR THE CANADIAN ELECTRICAL CODE (CEC), LOCAL CODES, AND THE INSTALLATION INSTRUCTIONS.
WARNING: RISK OF ELECTRICAL SHOCK. DISCONNECT ALL POWER SUPPLIES TO ENCLOSURE BEFORE EXPOSING INTERIOR. MORE THAN ONE SUPPLY DISCONNECT MAY BE REQUIRED TO DE-ENERGIZE THIS EQUIPMENT BEFORE SERVICING.
WARNING: SEPARATE OVERCURRENT PROTECTION MUST BE PROVIDED IN ACCORDANCE WITH THE NEC ARTICLE 220 OR CEC, SECTION B AS APPROPRIATE. OVER CURRENT PROTECTION MUST NOT EXCEED THE AMPERE RATING OF THE RECEPTACLE PER NEC SECTION 430-42 (C) OR CEC PART 1, RULE 28-602 (3)(C)(I).
OTHER CAUTIONS AND NOTES:
1. USE THIS DEVICE ONLY WITH COPPER OR COPPER CLAD WIRE.
2. CHECK TO SEE THAT RATING MARKED ON DEVICE IS CORRECT FOR THE INTENDED INSTALLATION.
Figure 1A: Non-Fused
Figure 1B: Fused
Figure 1C: Breakered
3. THE LOCKOUT FEATURE DOES NOT INTERRUPT THE POWER SUPPLIED TO THE SWITCH.
4. DEVICE IS SUITABLE FOR USE ON A CIRCUIT CAPABLE OF DELIVERING NOT MORE THAN 600 VAC MAXIMUM. FOR FUSED
LISTED CONDUIT HUB (NOT PROVIDED)
LISTED CONDUIT HUB (NOT PROVIDED)
LISTED CONDUIT HUB (NOT PROVIDED)
ITEMS, USE CLASS J FUSES.
TYPE 3R, 4X, 12K RATED
TYPE 3R, 4X, 12K RATED
TYPE 3R, 4X, 12K RATED
5. COVER CANNOT BE REMOVED WHEN HANDLE IS IN THE "ON" POSITION.
6. THIS ENCLOSURE MUST ALWAYS BE MOUNTED VERTICALLY WITH RECEPTACLE END DOWN.
TO INSTALL:
NOTE: Leviton Mechanical Interlocks may be mounted for Top or Bottom feed of supply wires (refer to Figure 1A, 1B and. 1C) .
Mounting:
1. Loosen the four (4) cover screws from the front cover (refer to Figure.2) .
2. Drill four (4) 1/4" (6.4 mm) diameter holes through the four corner wells on the inside back/rear of enclosure (refer to Figure 1A, 1B and
1C). If desired, or to meet Type 4x requirements, attach the four mounting feet to the rear of the enclosure using the hardware provided.
The mounting feet may be oriented in several positions. Tighten each foot screw to 18 in-lbs. (2 N-m) torque. Mounting feet holes accept up
to 5/16" (8.0 mm) diameter screws (not provided).
Top or Bottom Feed:
1. Drill points provided for top left, top right, bottom left conduit entry. NOTE: A metal closure plug must be grounded (bonded) back on to an
unused ground terminal.
Fitting sizes are as follows:
Mechanical Interlock rated for 20A and 30A – 1-1/2" (38.1 mm) diameter hole for 1" (25.4 mm) hub.
Mechanical Interlock rated for 60A – 2" (50.8 mm) diameter hole for 1-1/2" (38.1 mm) hub.
Mechanical Interlock rated for 100A – 1-1/2" (38.1 mm) diameter hole for 2" (50.8 mm) hub.
NOTE: Use of a UL Listed Watertight conduit fitting (not provided) is required to maintain the Type 3R, 4X and Type 12K rating
(refer to Figure 1A, 1B. and 1C)
2. Install the conduit fitting ensuring that the “O” ring is properly seated and the inside locking ring is seated tightly against the inside metal
frame to assure proper grounding (refer to Figure 1A, 1B and 1C).
3. When using Top feed conduit entrance, always form condensation drip loops in wiring as shown in Figure 1A, 1B and. 1C .
Wiring:
NOTE: Use conductors with insulation rated 75 C or higher having sufficient amacity in accordance with the 60 C column of Table 310-16 of
the NEC or Table 2 of the Canadian Electrical Code. DO NOT tin conductors.
1. WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS
OFF BEFORE WIRING! MAKE SURE CONNECTED EQUIPMENT RATING DOES NOT EXCEED THE RATING OF THIS DEVICE.
2. Strip all conductors approximately 11/16" (17.5 mm). For Auxiliary contact, strip conductors 5/16" (8.0 mm).
For Switch terminals, use conductor size ranges as follows:
Non-Fused or Breakered
Fused
20A and 30A
#14-#8 AWG.
20A and 30A
#14-#8 AWG.
60A
#14-#4 AWG.
60A
#14-#4 AWG.
100A
#8-#00 AWG.
For Neutral and Ground terminals, use conductor size ranges as follows:
Non-Fused or Breakered
Fused
20A and 30A
#14-#6 AWG.
20A and 30A
#14-#6 AWG.
60A
#10-#2 AWG. (Neutral terminal)
60A
#10-#2 AWG. (Neutral terminal)
60A
#10-#2 AWG. (Ground terminal)
60A
#10-#2 AWG. (Ground terminal)
100A
#8-#00 AWG. (Neutral terminal)
100A
#8-#2 AWG. (Ground terminal)
For Auxiliary terminals, use conductor size ranges as follows:
Non-Fused
Fused
20A and 30A
#18-#14 AWG.
20A and 30A
#18-#14 AWG.
60A
#18-#14 AWG.
60A
#18-#14 AWG.
100A
#18-#14 AWG.
3. Connect conductors per appropriate WIRING DIAGRAM.
4. Tighten all terminal screws as follows:
Switch terminals:
Non-Fused or Breakered
Fused
20A and 30A
7 in-lbs. (0.8 N-m)
20A and 30A
17 in-lbs. (2 N-m)
60A
18 in-lbs. (2 N-m)
60A
30 in-lbs. (3.4 N-m)
100A
55 in-lbs. (6.2 N-m)
Neutral and Ground terminals:
Non-Fused or Breakered
Fused
20A and 30A
19 in-lbs. (2 N-m)
20A and 30A
19 in-lbs. (2 N-m)
60A
60A
25.7 in-lbs. (2.9 N-m)
25.7 in-lbs. (2.9 N-m)
100A – Ground
25.7 in-lbs. (2.9 N-m)
100A – Neutral
57.5 in-lbs. (6.5 N-m)
Auxiliary contact:
NOTE: There is no auxiliary contact on Breakered Mechanical Interlock Receptacles.
All other devices – 5.3 in-lbs. (0.6 N-m)
5. Make sure that there are no stray conductor strands.
6. Ensure that the gasket is in place in cover groove. Replace cover and tighten cover screws to 22 in-lbs. (2.5 N-m) torque.
NOTE: Handle must be in the “OFF” position to install cover.
Fuses (not included):
For 20A devices, use Bussman LPJ20SP or Gould-Shawmut AJT20.
For 30A devices, use Bussman LPJ30SP or Gould-Shawmut AJT30.
For 60A devices, use Bussman LPJ60SP or Gould-Shawmut AJT60.
CAUTION: Amperage rating of fuses must not exceed the maximum ampere rating of this device. See front cover of device for maximum
ampere rating.
2CMC000028M0001, Rev B / May 2019
CONDUIT GROUNDING PLATE
ABB s.r.o.
Elektro-Praga
Resslova 3
466 02 Jablonec nad Nisou
Tel.: 800 800 104
E-mail: epj.jablonec@cz.abb.com
www.abb.com/industrialplugs
Figure 2: Front Cover
CONDUIT GROUNDING PLATE
CONDUIT GROUNDING PLATE
AUXILIARY CONTACT BUSS
NEUTRAL BUSS
GROUND BUSS
SWTCH
AUXILIARY CONTACT
FUSED
SWITCH
GROUND
BUSS
NEUTRAL
BUSS
CONDENSATION
DRIP
LOOPS
CONDENSATION
DRIP
LOOPS
DRILL HOLE
(4 PLACES)
DRILL HOLE
(4 PLACES)
SWITCH
AUXILIARY CONTACT
NEUTRAL BUSS
GROUND BUSS
CONDENSATION
DRIP
LOOPS
DRILL HOLE
(4 PLACES)
RATINGS
Table 1A: 20 and 30 Amp Type 3R, 4X, 12K Watertight Devices (Non-Fused)
20 Amp
Wiring
2P, 3W
2P, 3W
3P, 4W
3P, 4W
3P, 4W
3P, 4W
4P, 5W
4P, 5W
4P, 5W
30 Amp
2P, 3W
2P, 3W
2P, 3W
3P, 4W
3P, 4W
3P, 4W
3P, 4W
4P, 5W
4P, 5W
4P, 5W
Voltage, AC
250
480
125/250
3Ø 250
3Ø 480
3Ø 600
3ØY 120/208
3ØY 277/480
3ØY 347/600
125
250
480
125/250
3Ø 250
3Ø 480
3Ø 600
3ØY 120/208
3ØY 277/480
3ØY 347/600
Mechanical
Interlock
320MI6W
320MI7W
420MI12W
420MI9W
420MI7W
420MI5W
520MI9W
520MI7W
520MI5W
330MI4W
330MI6W
330MI7W
430MI12W
430MI9W
430MI7W
430MI5W
530MI9W
530MI7W
530MI5W
HP
Rating
3
5
*
10
20
25
10
20
25
*
5
10
*
10
20
25
10
20
25
Use Plug
Cat. No.
320P6W
320P7W
420P12W
420P9W
420P7W
420P5W
520P9W
520P7W
520P5W
330P4W
330P6W
330P7W
430P12W
430P9W
430P7W
430P5W
530P9W
530P7W
530P5W
Wiring
Diagram
A
A
G
E
E
E
J
J
J
B
A
A
G
E
E
E
J
J
J
Table 2A: 60 Amp Type 3R, 4X, 12K Watertight Devices (Non-Fused)
Mechanical
HP
Use Plug
Interlock
Rating
Cat. No.
Voltage, AC
Wiring
2P, 3W
2P, 3W
2P, 3W
3P, 4W
3P, 4W
3P, 4W
3P, 4W
4P, 5W
4P, 5W
4P, 5W
125
250
480
125/250
3Ø 250
3Ø 480
3Ø 600
3ØY 120/208
3ØY 277/480
3ØY 347/600
360MI4W
360MI6W
360MI7W
460MI12W
460MI9W
460MI7W
460MI5W
560MI9W
560MI7W
560MI5W
Wiring
Diagram
360P4W
360P6W
360P7W
460P12W
460P9W
460P7W
460P5W
560P9W
560P7W
560P5W
L
N
N
S
Q
Q
Q
U
U
U
HP
Rating
Use Plug
Cat. No.
Wiring
Diagram
*
15
25
*
30
30
*
50
50
50
25
25
50
50
3100P4W
3100P6W
3100P7W
4100P12W
4100P9W
4100P9W
4100P12W
4100P7W
4100P7W
4100P5W
5100P9W
5100P9W
5100P7W
5100P5W
L
N
N
S
Q
Q
Q
Q
Q
Q
U
U
U
U
*
10
20
*
20
40
40
20
40
40
Table 3A: 100 Amp Type 3R, 4X, 12K Watertight Devices
Wiring
Voltage, AC
Mechanical
Interlock
2P, 3W
2P, 5W
2P, 3W
3P, 4W
3P, 4W
3P, 4W
3P, 4W
3P, 4W
3P, 4W
3P, 4W
4P, 5W
4P, 5W
4P, 5W
4P, 5W
125
250
480
125/250
3 Ø 250
3 Ø 250
125/250
3 Ø 480
3Ø 480
3Ø 600
3Ø Y 120/208
Y
3Ø 120/208
3Ø Y 277/480
3Ø Y 347/600
3100MI4W
3100MI6W
3100MI7W
4100MI12W
4100MI9W
4100MB9W
4100MB12W
4100MB7W
4100MI7W
4100MI5W
5100MI9W
5100MB9W
5100MI7W
5100MI5W
Table 4A:
20A Type 3R, 4X, 12K Watertight Devices (Fused)
Wiring
3P, 4W
3P, 4W
3P, 4W
3P, 4W
Voltage, AC
125/250
3Ø 250
3Ø 480
3Ø 600
Mechanical
Interlock
420MF12W
420MF9W
420MF7W
420MF5W
HP
Rating
*
5
10
15
Use Plug
Cat. No.
420P12W
420P9W
420P7W
420P5W
Wiring
Diagram
H
F
F
F
Table 5A: 30A Type 3R, 4X, 12K Watertight Devices (Fused)
Wiring
Voltage, AC
Mechanical
Interlock
HP
Rating
Use Plug
Cat. No.
Wiring
Diagram
3P, 4W
3P, 4W
3P, 4W
3P, 4W
4P, 5W
4P, 5W
125/250
3Ø 250
3Ø 480
3Ø 600
3ØY 277/480
3ØY 347/600
430MF12W
430MF9W
430MF7W
430MF5W
530MF7W
530MF5W
*
7.5
15
20
15
20
430P12W
430P9W
430P7W
430P5W
530P7W
530P5W
H
F
F
F
K
K
Table 6A: 60A Type 3R, 4X, 12K Watertight Devices (Fused)
Wiring
Voltage, AC
Mechanical
Interlock
HP
Rating
Use Plug
Cat. No.
Wiring
Diagram
2P, 3W
3P, 4W
3P, 4W
3P, 4W
3P, 4W
4P, 5W
250
125/250
3Ø 250
3Ø 480
3Ø 600
3ØY 120/208
360MF6W
460MF12W
460MF9W
460MF7W
460MF5W
560MF9W
*
*
15
30
50
15
360P6W
460P12W
460P9W
460P7W
460P5W
560P9W
P
T
R
R
R
V
Wiring diagram A
20-30 Amps. Non-Fused
2-Pole, 3-Wire – Single Phase (No Neutral)
Wiring diagram C
20-30 Amps. Fused
2-Pole, 3-Wire – Single Phase
Wiring diagram B
20-30 Amps. Non-Fused
2-Pole, 3-Wire – Single Phase
G
W G
L
L1
L2
L
L3
L1
13
T1
T2
14
T3
AUXILIARY
CONTACT
GROUND BUSS
G
GROUND BUSS
L
G
L3
L2
HUB GROUNDING PLATE
HUB GROUNDING PLATE
13
14
T2
T3
L1
L3
L2
AUXILIARY
CONTACT
AUXILIARY
CONTACT
13
14
T1
T2
L2
G
GROUND BUSS
X
Y
Z
X
Y
Z
L1
L2
L3
L1
L2
L3
W G
T2
GROUND BUSS
L
L3
NEUTRAL
BUSS
13
14
T1
T3
GROUND BUSS
G
L
L
L1
Wiring diagram G
20-30 Amps. Non-Fused
3-Pole, 4-Wire – Edison System
GROUND BUSS
W
L
T1
Wiring diagram F
20-30 Amps. Fused
3-Pole, 4-Wire – 3 Phase
HUB GROUNDING PLATE
HUB GROUNDING PLATE
GROUND BUSS
Wiring diagram E
20-30 Amps. Non-Fused
3-Pole, 4-Wire – 3 Phase
HUB GROUNDING PLATE
HUB GROUNDING PLATE
HUB GROUNDING PLATE
Wiring diagram D
20-30 Amps. Fused
2-Pole, 3-Wire – Single Phase (No Neutral)
T3
AUXILIARY
CONTACT
13
14
T1
T2
AUXILIARY
CONTACT
AUXILIARY
CONTACT
13
14
T1
T3
T2
T3
L
L1
L2
L3
T1
T2
T3
13
14
AUXILIARY
CONTACT
N
L1
L2
Wiring diagram J
20-30 Amps. Non-Fused
4-Pole, 5-Wire – 3 Phase Y
Wiring diagram H
20-30 Amps. Fused
3-Pole, 4-Wire – Edison System
Wiring diagram L
60-100 Amps. Non-Fused
2-Pole, 3-Wire – Single Phase
Wiring diagram K
20-30 Amps. Fused
4-Pole, 5-Wire – 3 Phase Y
L2
L3
Wiring diagram M
60 Amps. Fused
2-Pole, 3-Wire – Single Phase
L3
Wiring diagram N
60-100 Amps. Non-Fused
2-Pole, 3-Wire – Single Phase (No Neutral)
HUB GROUNDING PLATE
GROUND BUSS
HUB GROUNDING PLATE
GROUND BUSS
G
W
L
G
W G
L1
L
NEUTRAL BUSS
L3
L2
AUXILIARY
CONTACT
13
14
T1
T2
T3
X
L3
L2
T1
T2
L3
L3
L2
T3
Y
L1
13
14
N
L1
NEUTRAL BUSS
L
L
L1
GROUND
BUSS
Z
G W
AUXILIARY
CONTACT
13
14
T1
L1
T2
L3
T3
L2
GROUND
BUSS
L
L1
13
T1
T2
T3
14
AUXILIARY
CONTACT
14
L2
L3
G
L
L
Wiring diagram S
60-100 Amps. Non-Fused
3-Pole, 4-Wire – Edison System
Wiring diagram T
60 Amps. Fused
3-Pole, 4-Wire – Edison System
W
G
AUXILIARY
CONTACTS
BUSS
HUB GROUNDING PLATE
L2
L1
L
G G
L1
13
T1
T2
T3
Y
Z
13
L3
14
AUXILIAR Y
CONT ACT
(NON-FUSED ONLY)
14
L2
G W
L
L2
L1
L3
T1
T2
13 14
Wiring diagram U
60-100 Amps. Non-Fused
or 100A Breakered
4-Pole, 5-Wire – 3 Phase Y
L3
GROUND
BUSS
L1
L3
13
14
T1
L1
2CMC000028M0001, Rev B / May 2019
L2
L3
14
AUXILIARY
CONTACT
Wiring diagram V
60 Amps. Fused
4-Pole, 5-Wire – 3 Phase Y
AUXILIARY
CONTACTS
BUSS
HUB GROUNDING PLATE
N G G
N
L
L2
T2
T3
AUXILIARY
CONTACT
AUXILIARY
CONTACT
T1
L3
14
T2
W
13 14
G
N G G
N
G W
SCREW ON
SWITCHBRACKET
X
Y
Z
L1
L2
L3
T1
T2
T3
T3
N
L3
NEUTRAL BUSS
X
Y
L1
L2
T1
T2
Z
13
13
14
AUXILIARY
CONTACT
(NON-FUSED ONLY)
14
L1
L3
L3
L2
L3
AUXILIARY
CONTACT
T3
NEUTRAL
BUSS
N
L2
T3
13
T3
G G N
T3
L1
T2
GROUND BUSS
NEUTRAL
BUSS
L1
T1
G
L
L
G G N
T2
L3
HUB GROUNDING PLATE
13
SCREW ON
SWITCHBRACKET
AUXILIARY
CONTACT
T1
L2
G G
GROUND
BUSS
X
L1
L1
NEUTRAL BUSS
GROUND
BUSS
L
G G
AUXILIARY
CONTACT
GROUND BUSS
13 14
G G
L
L
N
HUB GROUNDING PLATE
HUB GROUNDING PLATE
13 14
NEUTRAL
BUSS
HUB GROUNDING PLATE
GROUND BUSS
G
13
L3
L2
GG N
AUXILIARY
CONTACT
Wiring diagram R
60 Amps. Fused
3-Pole, 4-Wire – 3 Phase
AUXILIARY
CONTACT
BUSS
AUXILIARY
CONTACTS
BUSS
HUB GROUNDING PLATE
N G G
N
13 14
G
GROUND BUSS
NEUTRAL BUSS
L
L1
L3
L2
N
Wiring diagram Q
60-100 Amps. Non-Fused
or 100A Breakered
3-Pole, 4-Wire – 3 Phase
G
W
W
GROUND BUSS
NEUTRAL BUSS
L
AUXILIARY
CONTACT
BUSS
HUB GROUNDING PLATE
GROUND BUSS
Wiring diagram P
60 Amps. Fused
2-Pole, 3-Wire – Single Phase (No Neutral)
HUB GROUNDING PLATE
HUB GROUNDING PLATE
HUB GROUNDING PLATE
L3
L1
L1
L1
L3
N
N
L2
L1
SCREW ON
SWITCHBRACKET
AUXILIARY
CONTACT
L
L1
L2
T1
T2
13
14
L3
T3
SCREW ON SWITCHBRACKET
Prise à interverrouillage mécanique, à broches et à manchons, en logement étanche
20, 30, 60 et 100 (sans fusible)
20, 30, et 60 A (avec fusibles)
100A (avec disjoncteur)
DIRECTIVES
CARATÉRISTIQUES
•
•
•
•
Commutation de charges directement enfichées
Conformité aux codes en ce qui a trait aux installations intérieures (type 12K, étanchéité à la poussière) ou intérieures/extérieures (IP67, types 3R et 4X, étanchéité, résistance à la corrosion)
Logement verrouillable en position HORS TENSION (conformément aux exigences de l’OSHA – 29 CFR, partie 1910.147) au moyen d’un cadenas ou d’une manille acceptable, assurant que l’équipement connecté ne puisse être accidentellement mis sous tension
Ces contacts s’ouvrent avant les contacts principaux
REMARQUE : Ce logement ne peut être utilisé en guise de boîte de dérivation pour les connexions en passage continu.
ATTENTION
RISQUE DE CHOC ÉLECTRIQUE,
DÉCONNECTER L'ALIMENTATION
AVANT L'INSTALLATION.
ABB s.r.o.
Elektro-Praga
Resslova 3
466 02 Jablonec nad Nisou
Tel.: 800 800 104
E-mail: epj.jablonec@cz.abb.com
www.abb.com/industrialplugs
INSTALLATION
AVERTISSEMENT
: CES DISPOSITIFS NE PEUVENT ÊTRE INSTALLÉS QUE PAR UN ÉLECTRICIEN QUALIFIÉ CONFORMÉMENT AU NATIONAL ELECTRICAL CODE (NEC), AU CODE CANADIEN DE L’ÉLECTRICITÉ (CCÉ), AUX CODES LOCAUX ET AUX PRÉSENTES DIRECTIVES.
AVERTISSEMENT
: RISQUES DE CHOC ÉLECTRIQUE. DÉCONNECTER TOUTES LES SOURCES DE COURANT DU LOGEMENT AVANT D’EN EXPOSER L’INTÉRIEUR ET D’EN EFFECTUER LA MAINTENANCE (PLUS D’UNE DÉCONNEXION POURRAIT ÊTRE REQUISE).
AVERTISSEMENT
: ON DOIT ASSURER UNE PROTECTION DISTINCTE CONTRE LES SURINTENSITÉS,
CONFORMÉMENT
À L’ARTICLE 220 DU NEC OU À LA SECTION B DU CCÉ, SELON LE CAS; CETTE PROTECTION NE DOIT PAS DÉPASSER L’INTENSITÉ NOMINALE DE LA PRISE, SUIVANT LA SECTION 430-42(C) DU NEC OU DU RÈGLEMENT 28-602(3)(C)(I) DE LA PARTIE 1 DU CCÉ.
AUTRES REMARQUES ET MISES EN GARDE:
1. N’UTILISER CE DISPOSITIF QU’AVEC DU FIL DE CUIVRE OU PLAQUÉ CUIVRE .
2. S’ASSURER QUE LES VALEURS NOMINALES APPARAISSANT
SUR LE DISPOSITIF UTILISÉ CONVIENNENT BIEN À L’APPLICATION.
3. LE MÉCANISME DE VERROUILLAGE
N’AFFECTE EN RIEN L’ALIMENTATION DE L’INTERRUPTEUR.
4. CE DISPOSITIF CONVIENT AUX CIRCUITS CAPABLES DE LIVRER UN COURANT ALTERNATIF MAXIMAL, 600 VOLTS AU PLUS. EN PRÉSENCE
DE MODÈLES DOTÉS DE FUSIBLES, CES DERNIERS DOIVENT ÊTRE DE CLASSE « J » SEULEMENT.
5. ON NE PEUT RETIRER LE COUVERCLE
QUAND LA MANETTE EST EN POSITION SOUS TENSION (ON).
6. LE LOGEMENT DOIT ÊTRE INSTALLÉ À LA VERTICALE, EN METTANT LE CÔTÉ DE LA PRISE VERS LE BAS.
PROCÉDURE D’INSTALLATION :
Figure 1A: sans fusible
Figure 1B: avec fusibles
Figure 1C: avec disjoncteur
Figure 2: couvercle avant
REMARQUE : Les dispositifs à interverrouillage mécanique de Leviton peuvent être installés de manière à ce que les fils d’alimentation y
entrent par le haut ou par le bas (figures 1A, 1B et 1C) .
EMBOîTEMENT DE CONDUIT HOMOLOGUÉ ( NON FOURNI)
EMBOîTEMENT DE CONDUIT HOMOLOGUÉ (NON FOURNI)
EMBOîTEMENT DE CONDUIT HOMOLOGUÉ(NON FOURNI)
HOMOLOGATIONS 3R, 4X ET 12K
Fixation:
HOMOLOGATIONS 3R, 4X ET 12K
HOMOLOGA TIONS 3R, 4X ET 12K
1. Desserrer les quatre (4) vis d’assemblage du couvercle avant (figure 2) .
PLAQUE DE
PLA QUE DE
PLA QUE DE
MALT DU CONDUIT
MAL T DU CONDUIT
2. Percer un trou d’un diamètre d’un peu plus de 6 mm à travers chacun des quatre (4) orifices des coins arrières intérieurs du logement
MALT DU CONDUIT
(figures 1A, 1B et 1C) . Si désiré, ou pour répondre aux exigences d’une installation de type 4x, fixer les quatre pattes de montage à
l’arrière du logement au moyen des ferrures fournies. Ces pattes peuvent être orientées de diverses manières. Chacune des vis qui les
retiennent doit être serrée en appliquant un couple de 2 N.m. (18 po-lb). Les trous des pattes de montage acceptent les vis d’un diamètre
pouvant atteindre 8 mm (non comprises).
Alimentation par le haut ou par le bas:
CONTACTS BUS AUXILIAIRES
1. Des trous ont également été percés en haut à gauche, en haut à droite et en bas à gauche pour les installations où il est préférable de faire
BORNE DE TERRE
entrer le conduit à ces endroits.
BORNE NEUTRE
REMARQUE : Si on se sert d’un obturateur métallique, celui-ci doit être mis à la masse par le biais d’une borne de terre inutilisée.
Dimensions des raccords:
INTERRUPTEUR
BORNES AUXILIARES
INTERRUPTEUR
Interverrouillage mécanique, dispositifs de 20 et de 30 A : trou de 38,1 mm/emboîtement de 25,4 mm.
INTERR UPTEUR
Interverrouillage mécanique, dispositifs de 60 A : trou de 50,8 mm/emboîtement de 38,1 mm.
À FUSIBLES
BORNES
Interverrouillage mécanique, dispositifs de 100 A : trou de 38,1 mm/emboîtement de 50,8 mm.
AUXILIARES
BORNE
REMARQUE : On doit se servir d’un raccord de conduit étanche à acheter séparément fourni (homologation UL) pour rester conforme aux normes
DE
TERRE
de type 12K, 3R ou 4X (figures 1A, 1B et 1C) .
BOUCLES
BORNE
D'EGOUTTMENT
BOUCLES
2. Installer le raccord de conduit en vérifiant que la rondelle d’étanchéité soit uniformément appuyée et que la bague
NEUTRE
BORNE
DE CONDENSA TION
D'EGOUTTMENT
de blocage intérieure repose bien contre l’armature métallique, afin d’assurer une mise à la terre adéquate (figures 1A, 1B et 1C) .
NEUTRE
DE CONDENSATION
BORNE DE
BOUCLES
3. Si le conduit entre par le haut, on doit toujours former des boucles d’égouttement de condensation, tel qu’illustré aux figures 1A, 1B et 1C .
TERRE
D'EGOUTTMENT
Câblage :
DE CONDENSATION
PERCE
PERCE
REMARQUE : Les conducteurs utilisés doivent être dotés d’un isolant capable de résister à des températures de 75 °C ou plus ou doivent
UN TROU
UN TROU
PERCE
(4 ENDROITS)
présenter un courant admissible suffisant selon la colonne du 60 °C du tableau 2 du Code canadien de l’électricité ou du tableau 310-16 du
(4 ENDR OITS)
UN TROU
(4 ENDROITS)
National Electrical Code américain. NE PAS étamer les conducteurs!
1. AVERTISSEMENT
: POUR ÉVITER LES RISQUES D’INCENDIE, DE CHOC ÉLECTRIQUE OU D’ÉLECTROCUTION, COUPER
LE COURANT
AU FUSIBLE OU AU DISJONCTEUR
ET S’ASSURER QUE LE CIRCUIT SOIT BIEN COUPÉ AVANT DE PROCÉDER
À L’INSTALLATION. S’ASSURER QUE LA CHARGE NOMINALE DE L’ÉQUIPEMENT CONNECTÉ NE DÉPASSE PAS CELLE DU
DISPOSITIF À INSTALLER.
2. Dénuder les fils sur un peu plus de 1,5 cm (sauf ceux des bornes auxiliaires, qui doivent être dénudés sur à peine 1,0 cm).
Pour les bornes de l’interrupteur, se servir des données ci-dessous pour choisir le calibre de conducteur :
Sans fusible ou avec disjoncteur
Avec fusibles
Valeurs nominales
à #8 AWG.
20A et 30A
#14 à #8 AWG.
20A et 30A
60A
#14 à #4 AWG.
60A
#14 à #4 AWG.
100A
#8 à #00 AWG.
Tableau 2A: Dispositifs de 60 A, étanches de types 3R, 4X et 12K (sans fusible)
Tableau 1A: Dispositifs de 20 et de 30 A, étanches de types 3R, 4X et 12K (sans fusible)
Tableau 4A: Dispositifs de 20 A, étanches de types 3R, 4X et 12K (avec fusible)
Pour les bornes neutre et de terre, se servir des données ci-dessous pour choisir le calibre de conducteur:
20 A
Interverrouillage
Puissance
Schema
de
Interverrouillage
Puissance
Schema
de
Sans fusible ou avec disjoncteur
Avec fusibles
Interverrouillage
Puissance
Schema de
mécanique
nominale en ch
Câblage
Tension, c.a.
Finche N o
câblage
Finche N o
mécanique
nominale en ch
Câblage
Tension, c.a.
câblage
20 et 30A
#14 à #6 AWG.
20A et 30A
#14 à #6 AWG.
Câblage
Tension, c.a.
Fiche N o
mécanique
nominale en ch
câblage
360MI4W
320MI6W
3
2P, 3W
250
320P6W
A
#10 à #2 AWG. (borne neutre)
360P4W
L
2P, 3W
125
60A
#10 à #2 AWG. (borne
60A
*
125/250
420P12W
3P, 4W
420MF12W
*
H
10
#10 à #2 AWG. (borne de terre)
60A
#10 à #2 AWG. (borne de
250
360MI6W
320MI7W
5
2P, 3W
480
320P7W
A
60A
360P6W
2P, 3W
N
100A
#8 à #00 AWG. (borne neutre)
3Ø 250
420P9W
3P, 4W
420MF9W
5
F
20
480
360MI7W
420MI12W
*
3P, 4W
125/250
420P12W
G
360P7W
2P, 3W
N
100A
#8 à #2 AWG. (borne de terre)
3Ø 480
420P7W
3P, 4W
420MF7W
10
F
*
125/250
460MI12W
420MI9W
10
3P, 4W
3Ø 250
420P9W
E
460P12W
3P, 4W
S
Pour les bornes auxiliaires, se servir des données ci-dessous pour choisir le calibre de conducteur:
3Ø 600
420P5W
3P, 4W
420MF5W
15
F
20
3Ø 250
460MI9W
460P9W
3P, 4W
420MI7W
20
3Ø 480
3P, 4W
420P7W
E
Q
Sans fusible
Avec fusibles
40
3Ø 480
460MI7W
460P7W
3P, 4W
Q
420MI5W
25
3Ø 600
3P, 4W
420P5W
E
20 et 30A
#18 à #14 AWG.
20A et 30A
#18 à #14 AWG.
40
3Ø 600
460MI5W
460P5W
3P, 4W
Q
520MI9W
10
3ØY 120/208
4P, 5W
520P9W
J
60A
#18 à #14 AWG.
60A
#18 à #14 AWG.
Tableau 5A: Dispositifs de 30 A, étanches de types 3R, 4X et 12K (avec fusible)
100A
#18 à #14 AWG.
20
560MI9W
3ØY 120/208
560P9W
4P, 5W
U
520MI7W
20
4P, 5W
3ØY 277/480
520P7W
J
3. Raccorder les fils conformément au SCHÉMA DE CÂBLAGE approprié.
Puissance
40
Schema de
Interverrouillage
560MI7W
560P7W
3ØY 277/480
4P, 5W
U
520MI5W
25
4P, 5W
3ØY 347/600
520P5W
J
4. Serrer toutes les bornes à vis comme suit :
nominale en ch
Câblage
câblage
Fiche N o
mécanique
Tension, c.a.
560P5W
40
560MI5W
4P, 5W
3ØY 347/600
U
30 A
Borne de l’interrupteur :
*
H
430P12W
430MF12W
125/250
B
2P, 3W
125
330MI3W
3P,
4W
*
330P3W
Tableau 3A: Dispositifs de 100 A, étanches de types 3R, 4X et 12K (sans fusible)
Sans fusible ou avec disjoncteur
Avec fusibles
7.5
F
430P9W
430MF9W
330MI6W
5
2P, 3W
250
330P6W
A
3Ø 250
3P, 4W
20 et 30A
7po-lb(0,8 N.m.)
20A et 30A
17 po-lb (2 N.m.)
Puissance
Schema de
Interverrouillage
15
F
430P7W
430MF7W
330MI7W
10
2P, 3W
480
330P7W
A
3Ø 480
3P, 4W
60A
18 po-lb (2 N.m.)
60A
30 po-lb (3,4 N.m.)
nominale en ch
câblage
mécanique
Tension, c.a.
Finche N o
Câblage
20
F
430P5W
430MF5W
100A
55 po-lb (6,2 N.m.)
*
430MI12W
3P, 4W
125/250
430P12W
G
3Ø 600
3P, 4W
125
*
3100MI4W
2P, 3W
Bornes neutre et de terre:
3100P4W
L
15
K
530P7W
530MF7W
10
430MI9W
3P, 4W
3Ø 250
430P9W
E
4P, 5W 3ØY 277/480
250
Sans fusible ou avec disjoncteur
Avec fusibles
3100MI6W
15
2P, 5W
3100P6W
N
20
K
530P5W
530MF5W
20
430MI7W
3P, 4W
3Ø 480
430P7W
E
4P, 5W 3ØY 347/600
20A et 30A
19 po-lb (2 N.m.)
20A et 30A
19 po-lb (2 N.m.)
480
3100MI7W
25
2P, 3W
3100P7W
N
25
430MI5W
3P, 4W
3Ø 600
430P5W
E
60A
25.7 po-lb (2.9 N.m.)
60A
25.7 po-lb (2.9 N.m.)
125/250
4100MI12W
3P,
4W
4100P12W
S
*
10
530MI9W
3ØY 120/208
4P, 5W
530P9W
J
25.7 po-lb (2.9 N.m.)
100A – Terre
Tableau 6A: Dispositifs de 60 A, étanches de types 3R, 4X et 12K (avec fusible)
3Ø 250
4100MI9W
3P, 4W
4100P9W
Q
30
20
530MI7W
3ØY 277/480
4P, 5W
530P7W
J
100A – Neutre
57.5 po-lb (6.5 N.m.)
3
250
Ø
4100MB12W
3P, 4W
4100P12W
Q
30
Schema de
25
530MI5W
3ØY 347/600
4P, 5W
Puissance
530P5W
J
Interverrouillage
Bornes auxiliaires :
3Ø 250
4100MB9W
4100P9W
Q
3P, 4W
30
câblage
Câblage
nominale en ch
Fiche N o
mécanique
REMARQUE: Aucun contact auxiliaire n'est présent dans le cas des prises à interverrouillage mécanique avec disjoncteur.
Tension, c.a.
3Ø 480
4100MB7W
4100P7W
Q
3P, 4W
50
All devices – 5.3 po-lb (0,6 N.m.)
P
*
360P6W
360MF6W
250
2P, 3W
3Ø 480
4100MI7W
50
4100P7W
Q
5. S'assurer qu'aucun brin ne dépasse.
3P, 4W
T
*
460P12W
460MF12W
125/250
3P, 4W
6. S'assurer que le serrer les vis en appliquant un couple de 2,5 N.m. (22 po-lb).
50
3Ø 600
4100P5W
Q
4100MI5W
3P, 4W
R
15
460P9W
460MF9W
3Ø
250
3P,
4W
REMARQUE: Le couvercle ne pourra être installé que si la manette est en position hors tension (OFF).
25
5100P9W
U
5100MI9W
3ØY 120/208
4P, 5W
R
30
460P7W
460MF7W
3Ø 480
3P, 4W
Fusibles (non compris) :
25
5100P9W
U
5100MB9W
3ØY 120/208
4P, 5W
R
50
460P5W
460MF5W
3Ø 600
3P, 4W
Dispositifs de 20 A : Bussman LPJ20SP ou Gould-Shawmut AJT20.
50
5100P7W
U
5100MI7W
3ØY 277/480
4P, 5W
V
15
560P9W
560MF9W
Dispositifs de 30 A : Bussman LPJ30SP ou Gould-Shawmut AJT30.
4P, 5W 3ØY 120/208
50
5100P5W
U
5100MI5W
4P,
5W
347/600
3ØY
Dispositifs de 60 A : Bussman LPJ60SP ou Gould-Shawmut AJT60.
MISE EN GARDE :
L'intensité nominale des fusibles ne doit pas dépasser celle du dispositif utilisé, laquelle est indiquée sur le couvercle
avant de ce dernier.
2CMC000028M0001, Rev B / May 2019
Schéma de câblage A
20-30 A Sans fusibles
2-P, 3-F – Système monophasé (pas de neutre)
Schéma de câblage D
20-30 A Avec fusibles
2-P, 3-F – Système monophasé (pas de neutre)
Schéma de câblage C
20-30 A Avec fusibles
2-P, 3-F – Système monophasé
Schéma de câblage B
20-30 A Sans fusibles
2-P, 3-F – Système monophasé
PLAQUE DE MALT DU CONDUIT
W
BORNE DE
TERRE
L
L1
L2
L
L3
L1
14
T2
L3
L2
13
14
T1
T3
T2
13
BORNES
AUXILIARES
T2
BORNE DE
TERRE
Y
Z
X
Y
Z
L1
L2
L3
L1
L2
L3
L
BORNE
NEUTRE
13
BORNES
AUXILIARES
14
T1
T3
X
L3
BORNES
AUXILIARES
14
T1
L2
L1
L3
G
L
L
L2
W
G
G
BORNE
NEUTRE
L1
BORNE DE
TERRE
BORNE DE
TERRE
W
L
BORNES
AUXILIARES
T3
PLAQUE DE MALT DU CONDUIT
G
G
BORNE DE
TERRE
L
13
T1
G
PLAQUE DE MALT DU CONDUIT
BORNE DE
TERRE
BORNE DE
TERRE
G
Schéma de câblage G
20-30 A Sans fusibles
3-P, 4-F – Système Edison
PLAQUE DE MALT DU CONDUIT
PLAQUE DE MALT DU CONDUIT
PLAQUE DE MALT DU CONDUIT
PLAQUE DE MALT DU CONDUIT
Schéma de câblage F
20-30 A Avec fusibles
3-P, 4-F – Système triphasé
Schéma de câblage E
20-30 A Sans fusibles
3-P, 4-F – Système triphasé
T2
BORNES
AUXILIARES
14
T1
T2
L1
L2
L3
T1
T2
T3
13
13
T3
L
13
BORNES
AUXILIARES
14
T1
T3
T2
14
BORNES
AUXILIARES
T3
N
L1
L1
Schéma de câblage J
20-30 A Sans fusibles
4-P, 5-F – Système triphasé en étoile
Schéma de câblage H
20-30 A Avec fusibles
3-P, 4-F – Système Edison
Schéma de câblage K
20-30 A Avec fusibles
4-P, 5-F – Système triphasé en étoile
Schéma de câblage L
60-100 A Sans fusibles
2-P, 3-F – Système monophasé
L3
L1
L2
L2
L3
L3
Schéma de câblage N
60-100 A Sans fusibles
2-P, 3-F – Système monophasé (pas de neutre)
Schéma de câblage M
60 A Avec fusibles
2-P, 3-F – Système monophasé
Schéma de câblage P
60 A Avec fusibles
2-P, 3-F – Système monophasé (pas de neutre)
PLAQUE DE MALT DU CONDUIT
PLA QUE DE MALT DU CONDUIT
PLAQUE DE MALT DU CONDUIT
BORNES
AUXILIARES
PLAQUE DE MALT DU CONDUIT
G
W
G
BORNE
NEUTRE
L1
L
X
Y
L1
T2
13
BORNES
AUXILIARES
14
BORNE DE
TERRE
Z
G
W
L3
L2
L1
13
T1
L
L
BORNES
AUXILIARES
G
PLAQUE DE MALT DU CONDUIT
L
L
BORNE DE
TERRE
G
L
L
14
T1
T3
T2
L1
L3
L2
G
BORNES
AUXILIARES
13
T3
T1
T2
N
G
BORNES
AUXILIARES
14
L1
L3
L2
13
14
T1
T3
T2
14
L2
T3
CONTACT
AUXILIAIRE
T1
T2
L2
L1
G
13
14
T3
T1
T2
BORNES
AUXILIARES
T3
L2
N
L1
L3
L2
L1
L3
L3
N
N
Schéma de câblage Q
60-100 A Sans fusibles
ou avec disjoncteur
3-P, 4-F – Système triphasé
Schéma de câblage R
60 A Avec fusibles
3-P, 4-F – Système triphasé
Schéma de câblage S
60-100 A Sans fusibles
3-P, 4-F – Système Edison
Schéma de câblage T
60 A Avec fusibles
3-P, 4-F – Système Edison
Schéma de câblage U
60-100 A Sans fusibles
ou avec disjoncteur
4-P, 5-F – Système triphasé en étoile
PLAQUE DE MALT DU CONDUIT
Schéma de câblage V
60 A Avec fusibles
4-P, 5-F – Système triphasé en étoile
PLAQUE DE MALT DU CONDUIT
PLAQUE DE MALT DU CONDUIT
PLAQUE DE MALT DU CONDUIT
G
L
L
L2
14
T2
T3
BORNES
AUXILIAIRES
(sans fusibles
seulement)
X
Y
L1
L2
BORNE DE
TERRE
Z
13
14
N G
N
G
L3
G
W
13
L1
VIS SUR SWITCHSUPPORT
L2
L1
G
CONTACT
AUXILIAIRE
G
G
L2
L3
14
L2
T2
T3
N
13
T1
T2
T3
CONTACT
AUXILIAIRE
T1
T2
L1
L2
2CMC000028M0001, Rev B / May 2019
L3
Y
Z
VIS SUR SWITCHSUPPORT
X
Z
Y
13
L1
L2
L3
T3
T1
T2
T3
N
L1
L2
T1
T2
14
L3
13
BORNES
AUXILIAIRES
(sans fusibles
seulement)
T3
L2
N
L3
G
BORNE
NEUTRE
N
L1
X
14
BORNES
AUXILIARES
BORNE
NEUTRE
L3
G
N
L3
14
T1
W
L
L
L
L
G
BORNE
NEUTRE
BORNE DE
TERRE
G
L1
BORNES
AUXILIARES
PLAQUE DE MALT DU CONDUIT
BORNE
NEUTRE
13
G
W
BORNE DE
TERRE
13 14
PLAQUE DE MALT DU CONDUIT
G
L3
G G
T1
G
G
BORNES
AUXILIARES
BORNES
AUXILIARES
L
13 14
L1
BORNE DE
TERRE
G
BORNE DE
TERRE
BORNE DE
TERRE
W
L1
L3
L3
L1
L2
L3
N
N
L
L3
BORNE
NEUTRE
L1
G
L
L3
G
BORNES
AUXILIARES
G
BORNE
NEUTRE
13
BORNE
NEUTRE
L3
L2
BORNE
NEUTRE
NEUTRAL BUSS
L
N G
N
13 14
W
BORNE DE
TERRE
W
L
13 14
G
G
BORNE DE
TERRE
PLAQUE DE MALT DU CONDUIT
BORNE DE
TERRE
BORNE DE
TERRE
G
W
BORNE DE
TERRE
PLAQUE DE MALT DU CONDUIT
L1
BORNES
AUXILIARES
CONTACT
AUXILIAIRE
L1
L2
T1
T2
13
14
L3
T3
VIS SUR SWITCHSUPPORT

Manuels associés